Wuhan Huaying Electric Power Tech & Science Co., Ltd

20 YEARS experience in design and manufacture Hipot Test Set
Export to 50 Countries Worldwide
Professional Technical Support
ISO/CE/CNAS/SGS Certificate

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsVLF Test Set

AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz

Good quality CT PT Test Set for sales
Good quality CT PT Test Set for sales
We are very happy with oil tester and TTR tester puchased from your company.

—— Jim

We are pleased of your product.It's going on smoothly.

—— Md Monabbir

I'm Online Chat Now

AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz

China AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz supplier
AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz supplier AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz supplier AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz supplier

Large Image :  AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz

Product Details:

Place of Origin: Wuhan Hubei China
Brand Name: Huaying
Certification: ISO, CE
Model Number: VLF

Payment & Shipping Terms:

Minimum Order Quantity: 1 Set
Price: Negotiable
Packaging Details: Wooden Case
Delivery Time: 7 Working Days
Payment Terms: T/T L/C
Supply Ability: 200 sets per month
Contact Now
Detailed Product Description
Warranty: 1 Year Free And Lifelong Maintenance Customize Service: Accepted
Product Name:: AC Hipot Test Set Output Voltage:: 30kV, 50kV, 60kV, 80kV Or Others
Capacity: 0.6kVA ~ 2.4kVA Power Supply: AC 220V 50Hz

AC Hipot Test Set High Voltage Tester VLF Cable Testing Equipment AC 220V 50Hz

 

1. Product Name: VLF Very low Frequency Tester

 

2. Equipment Description:

 

The VLF testers (Generator) are suitable for
Testing cables, transformers, switchgear,
Rotating machinery, and other
Electrical apparatus.

 

(A). Main Functions:
1. Easiest to use Fully automatic microcontroller
2. Built-in printer
3. True sine wave output
4. Real-time display of actual output waveform
5. Ergonomic, menu guided, large backlit LCD
6. Storage of test results for later retrieval and print.
7. Over voltage and current protected
8. Variable frequency 0.1Hz, 0.05Hz, 0.02 Hz
9. Data of current, voltage and waveform directly sampled at HV side.
10. AC testing does not degrade good cable insulation
11. Harmful space charges are not injected into the cable insulation
12. No traveling waves are generated during testing
13. Rugged and reliable design less prone to failure from transients


(B). Specifications:
1. Input: 220 ± 10% Volts AC, 50/60 Hz, single phase.
2. Output-Voltage. 50KV
3. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz.
4. Stability of frequency: Fluctuation < 0.5%
5. Measurement accuracy: ± 3%.
6. Positive and negative voltage peak errors: ≤ 3%.
7. Voltage waveform distortion: ≤ 5%
8. Construction: In two units: Controller and Booster...
9. Ambient conditions of use: Temperature Indoor and outdoor: -10ºC to + 50ºC.
10. Humidity: ≤ 85%

 

3. Models:


Type

Output
Voltage/Current

Load Capacity

Control Unit

Booster

Fuse Tube


Frequency/Capacitance

Dim.
(cm)

Wt
(kg)

Dim.
(cm)

Wt
(kg)

VLF-30/1.1

30KV/20mA

0.1Hz ≤ 1.1uF
0.05Hz ≤ 2.2uF
0.02Hz ≤ 5.5uF

28× 37× 22

4

33× 18× 34

25

5A

VLF-40/1.1

40KV/30mA

0.1Hz ≤ 1.1uF
0.05Hz ≤ 2.2uF
0.02Hz ≤ 5.5uF

28× 37× 22

4

35× 20× 36

35

6A

VLF-50/1.1

50KV/40mA

0.1Hz ≤ 1.1uF
0.05Hz ≤ 2.2uF
0.02Hz ≤ 5.5uF

28× 37× 22

4

37× 24× 39

45

7A

VLF-60/1.1

60KV/50mA

0.1Hz ≤ 1.1uF
0.05Hz ≤ 2.2uF
0.02Hz ≤ 5.5uF

28× 37× 22

4

33× 18× 34
33× 18× 34

25+25

10A

VLF-70/0.5

70KV/55mA

0.1 Hz, ≤ 0.5µ F
0.05Hz, ≤ 1.0µ F
0.02Hz, ≤ 2.5µ F

28× 37× 22

4


33× 18× 34
35× 20× 36

25+35

10A

VLF-80/0.5

80KV/60mA

0.1 Hz, ≤ 0.5µ F
0.05Hz, ≤ 1.0µ F
0.02Hz, ≤ 2.5µ F

28× 37× 22

4

33× 18× 34
37× 24× 39

25+45

12A

 

Accompanied accessories:


1. One special high-voltage connecting cable
2. One special low-voltage connecting cable
3. One power cable
4. Ten power supply fuse tubes
13
5. One discharging rod
6. One compensation capacitor
7. One control unit
8. One booster
9. One grounding cable
10. Two rolls of printer paper